CBXi IP Controller | CBXi Web UI
©ABB 2022 All Rights Reserved.
Subject to change without notice
WWW.CYLON.COM
19
ROUTER NETWORKS
BACnet Network numbers are used to identify thewire” to which the device is attached.
For IP, all devices on the local LAN must have the same BACnet Network number.
For MS/TP devices, each serial bus line must have a unique BACnet Network number.
TIME SYNC
BACnet Time Synchronization messages can be sent from this device to any BACnet device in order to
ensure that those devices have the correct times.
The Transmit Options control how often and when to send.
The Destinations list the targets to which the Time Sync messages will be sent.
Time Sync messages can be broadcast to an entire network if desired.