RESTARTING AND RESETTING THE CBXi
The CBXi controller can be restarted or reset using the two switches located on the front panel (under
the flap) beside the LED:
RESETTING THE WEBUI LOGIN
If the WebUI username / password or IP address have been changed to unknown values so that you
cannot log in to the WebUI, you can reset them to known values, i.e.
• username:
admin
• password:
cylonctl
• IP address: based on serial number (see
Configuring the IP connection
on page 31)
To reset the IP address and password, press SW1 while the controller is running, hold it until the LED
lights up, and then release SW1.
FULL FACTORY RESET
To restore all settings in the CBXi, including any strategy configuration, press SW1 while the controller is
booting, hold it until the LED lights up, and then release SW1.
RESTARTING THE CONTROLLER WITHOUT POWER CYCLING
To restart the CBXi without disconnecting the power, press SW2 while the controller is running, hold it
until the LED lights up, and then release SW2.