Wiring with the logic relay
148
1SVC 440 795 M0100
Timing relays The logic relay provides 16 timing relays from T 1 to T 16.
A timing relay is used to change the switching duration and 
the make and break times of a switching contact. The delay 
times can be configured between 2 ms and 99 h 59 min. You 
can use positive values, values of analog inputs, actual 
values of counter relays and timing relays.
You can also use the logic relay as a multi-function relay in 
the application. The logic relay is more flexible than any 
hardwired timing relay since you can wire all the functions at 
the push of a button as well as program additional functions.
You integrate a timing relay into your circuit in the form of a 
contact and coil.
h
The timing relays of CL-LSR/CL-LST and CL-LMR/CL-LMT 
function in the same way as the timing relays of the 
AC010 devices.
Exception: The “flasher” function starts on the CL-LSR/
CL-LST and CL-LMR/CL-LMT with the pulse. With the 
AC010, the “flasher” function starts with the pause. If 
required, the same timing relays can also be used for 
retentive data.
I1-I4----TT1
T1-------ÄQ3
Contact Coil
T1 to T16  Contact of a timing relay
TT1 to TT16  Enable, timing relay trigger
RT1 to RT16  reset coil of the timing relay
HT1 to HT16  stop coil of the timing relay
(H = Stop , S means the set coil 
function)
h
To prevent unpredictable switching states, use each coil of 
a relay once only in the circuit diagram.