CL settings
222
1SVC 440 795 M0100
Setting retentive behaviour
Requirement: the logic relay must be in STOP mode.
X Switch to the system menu.
X Switch to STOP mode.
X Switch to the system menu.
X Move to the SYSTEM menu and continue to the 
RETENTION… menu.
X Press the OK button.
The first screen display is the selection of the marker range.
X ÍÚ Select a range. 
X Press OK to select the marker, the function relay or the 
range that is to be retentive (tick on the line).
Press ESC to exit the input for the retentive ranges.
Example: 
M9 to M12, counters C5 to C7, C8 as well as timing relays 
T7 and T8 are retentive. Indicated by the tick on the line. 
The default setting of the logic relay is selected so that no 
retentive data is selected. In this setting, the logic relay 
works without retentive actual values if a valid circuit 
diagram is present. When the logic relay is in STOP mode or 
has been switched to a de-energized state, all actual values 
are cleared.
h
If the logic relay is protected by a password, the system 
menu will not be available until the logic relay is 
“unlocked” (a section “Unlock logic relay”, from 
Page 199).
RUN MODE  åÆ
CARD MODE
CYCLE-T...
RETENTION  æ
M 9 - M12 åÆ
M13 - M16
N 9 - N16
C 5 - C 7 åæ
C 8   å
C13 - C16
D 1 - D 8
T7
T8
T13 - T16
M 9 - M12 åÆ
M13 - M16
N 9 - N16
C 5 - C 7 åæ
C 8   å
C13 - C16
D 1 - D 8
T 7  å
T 8  å
T13 - T16