EasyManuals Logo

ABB DCS800 Installation And Start-Up Manual

ABB DCS800
66 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
23
Hardware
3ADW000197R0101 DCS800-R Sel e a
Voltage coding
Use the settings given by the next table. Depending on the line voltage applied to
the existing power stack the jumpers need to be removed accordingly (lower line
voltage scaling on request).
Note:
At existing power parts with high supply voltage the option galvanic isolation
should be taken into consideration because of personal and functional safety rea-
sons.
appr.
200...500 V
500 600 690 800
1000
W1, 6, 12, 17, 22
W2, 7, 13, 18, 23
W3, 8, 14, 19, 24
W4, 9, 15, 20, 25
W5, 11, 16, 21, 26
to the power stack
Voltage applied
Value for
S ConvScaleVolt (97.03)
indicates a removed jumper
501...600 V 601...700 V 701...800 V 801...990 V
Nominal current coding
At first make sure, that the current transformers are mounted and wired according
to the figure before.
In addition to that two other definitions are important:
the nominal current I
dN
is equivalent to 1.5 V across the nominal current
burden resistors
the current measurement is designed to handle peak currents up to two-
times of I
dN
Most often the current I
dN
is the thermal current of the existing power part (thyristor
stack); the peak current may be the highest current running through the motor.
If the peak current is higher than two-times I
dN
the
nominal current needs to be redefined.
The value
peakdNDCR
II *5.0=
has to be used instead of
I
dN
at all the next equations!
The scaling for nominal current will be done by the resistors R1 to R21, which
are connected in parallel.

Table of Contents

Other manuals for ABB DCS800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB DCS800 and is the answer not in the manual?

ABB DCS800 Specifications

General IconGeneral
Control TypeDigital
Supply Voltage380 ... 690 V AC
Input Voltage Range380 V to 690 V AC
Control ModeTorque, Speed
Cooling MethodAir-cooled
Communication ProtocolsModbus, Profibus, CANopen
Communication OptionsEthernet
Protection ClassIP21, IP54
Enclosure RatingIP00, IP21, IP54
ProtectionOvercurrent, Overvoltage, Overtemperature
Ambient Temperature0 to 40°C
Field SupplyIntegrated or External

Related product manuals