EasyManua.ls Logo

ABB EasyLine EL3000 - Page 70

ABB EasyLine EL3000
216 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
70 EL3000 CONTINUOUS GAS ANALYZERS | OI/EL3000-EN REV. D
5 Installation
Position and design of the gas connections
Gas connections Magnos206 (model EL3040)
Figure 21: Gas connections Magnos206 (model EL3040)
Magnos206: Gas Connections
Pos.
Connection
Supplementary information
Version
1
Sample gas inlet
⅛ NPT female thread (stainless steel 1.4305)
Connection of hose lines:
straight screw-in socket (PP) with hose nozzles for
hoses with inside diameter 4 mm
(included in scope of delivery)
Connection of piping:
screw-in fittings
(not included in scope of delivery)
2
Sample gas outlet
3
Not assigned
4
Not assigned
11
Purge gas inlet
(housing)
12
Purge gas outlet
(housing)
13
Pressure sensor
14
Not assigned
Note
The pressure sensor (see Pressure sensor on page 36) is installed as an option.
For a precise pressure correction as well as for measurements in suppressed measuring ranges, the sensor and sample gas outlet
have to be connected to each other via a T-piece and with the use of short conductors.
The lines must be as short as possible or in the case of a greater length have a sufficiently large inside diameter (min. 10 mm) so
that the flow effect is minimized.