EtherNet/IP Start-up 147
The table below gives the recommended drive parameter settings.
Drive parameter Setting for ACS880
/ACS580 drives
Description
50.01 FBA A enable 1 = Option slot 1
2)
Enables communication between
the drive and the fieldbus adapter
module.
50.02 FBA A comm loss
func
1 = Fault
2)
Enables fieldbus A
communication fault monitoring.
50.03 FBA A comm loss t
out
3.0 s
2)
Defines the fieldbus A
communication break supervision
time.
50.04 FBA A ref1 type 4 = Speed Selects the fieldbus A reference 1
type and scaling.
51.01 FBA A type 128 = ETHERNET
1)
Displays the type of the fieldbus
adapter module.
51.02 Protocol/Profile 100 = EIP AC/DC Selects the EtherNet/IP protocol
and the ODVA AC/DC drive
profile.
51.03 Commrate 0 = Auto
2)
Ethernet communication rate is
negotiated automatically by the
device.
51.04 IP configuration 0 = Static IP
2)
Configuration will be obtained
from configuration parameters
0513.
51.05 IP address 1 192
2)
First part of the IP address
51.06 IP address 2 168
2)
Second part of the IP address
51.07 IP address 3 0
2)
Third part of the IP address
51.08 IP address 4 16
2)
Last part of the IP address
51.09 Subnet CIDR 24
2)
Sets the network mask as
255.255.255.0, allowing access
only to the last subnet.
51.23 ODVA speed scale 128
2)
Sets the scaling for the ODVA
speed reference.
52.01 FBA data in1 01.14
2)
Output power
52.03 FBA data in3 01.11
2)
DC voltage
53.01 FBA data out1 22.26
2)
Constant speed 1
53.03 FBA data out3 22.27
2)
Constant speed 2