PROFINET IO – Start-up 285
The table below gives the recommended drive parameter settings.
Drive parameter Setting for ACS880
drives
Description
50.01 FBA A enable 1 = Option slot 1
2)
Enables communication between
the drive and the fieldbus adapter
module.
50.04 FBA A ref1 type 4 = Speed Selects the fieldbus A reference 1
type and scaling.
50.07 FBA A act1 type 0 = Auto Selects the actual value type and
scaling according to the currently
active Ref1 mode defined in
parameter 50.04.
51.01 FBA A type 128 = ETHERNET
1)
Displays the type of the fieldbus
adapter module.
51.02 Protocol/Profile 10 = PNIO Pdrive Selects the PROFINET IO
protocol and the PROFIdrive
profile.
51.03 Commrate 0 = Auto
2)
Ethernet communication rate is
negotiated automatically by the
device.
51.04 IP configuration 0 = Static IP Configuration will be obtained
from parameters 05…13 or from
the PLC via the DCP protocol.
52.01 FBA data in1 4 = SW 16bit
1)
Status word
52.02 FBA data in2 5 = Act1 16bit Actual value 1
52.03 FBA data in3 01.14 Output power
52.05 FBA data in5 01.11 DC voltage
53.01 FBA data out1 1 = CW 16bit
1)
Control word
53.02 FBA data out2 2 = Ref1 16bit Reference 1 (speed)
53.03 FBA data out3 22.26 Constant speed 1
53.05 FBA data out5 22.27 Constant speed 2
51.27 FBA A par refresh 1 = Refresh Validates the FENA-11/-21
configuration parameter settings.
19.12 Ext1 control mode 2 = Speed Selects speed control as the
control mode 1 for external control
location 1.