288 PROFINET IO – Start-up
The start sequence for the parameter example above is given
below.
Control word:
• Reset the fieldbus communication fault (if active).
• Enter 47Eh (1150 decimal) –> READY TO SWITCH ON.
• Enter 47Fh (1151 decimal) –> OPERATING (Scalar motor
control mode).
20.01 Ext1 commands 12 = Fieldbus A Selects the fieldbus A interface as
the source of the start and stop
commands for external control
location 1.
22.11 Speed ref1 source 4 = FB A ref1 Selects the fieldbus A reference 1
as the source for speed reference
1.