Page 107
© Copyright 2021 ABB. All rights reserved.
Large Fuses
for Groups 56 or 72
Comcode
Size
(A)
Wire Ga
(min)
408472322 70-250A Head --
405673161
0.18A Alarm Fuse --
406794776
70 6
408239648
80 4
406794784
100 2
406925685
125 2
406794792
150 1/0
406794818
200 4/0
406794982
225 4/0
406794842
250 4/0
406794867
300 (2) 4/0*
406794875
400 (2) 4/0*
406794883
500 (2) 4/0*
406794891
600 350*
3150002P-19
800** (2) 350*
*
Cables must be the same length and terminate at a common at each end.
** 800A Fuse only available with G72
Figure 8-14: ED83143-31 Group 56 (Deactivated) 1200A or Group 72 1280A (H469-434/4827/4830 G59, 59A) DC Distribution Panel
Shunt Monitoring Connection Points
to RPMs
1500A / 50mV Shunt
TB1-1 Upper Fuse –
TB1-2 Upper Fuse +
TB3-2 Lower Fuse –
TB3-3 Lower Fuse +
847073731 Bolt Kit
Torque to 240 in-lbs (27 Nm)
To DC Loads
(2) 405673161
Alarm Fuses
Distribution Panels (continued)
ED83143-31 Group 56
TPL-B
TPL-C
G72 Only