BLJ2/3 to BIC10 or BIC10 to BIC10 (Millennium II Controller)
The cable used in this procedure is:
Rectifier Interface Cable Assembly 847690799 (10 feet) (provided with cabinet)
Refer to Figure 6 - 7 for this procedure.
BLJ2/3 to BIC10 or BIC10 to BIC10 (Millennium II Controller)
Step Action
Connect the Rectifier Interface Cable Assembly from J5 of one BLJ2/3 board to any J1 - J4 of the BIC10 board in the
next cabinet or from any of J1 to J4 of one BIC 10 to any of J1 to J4 of the next BIC10.
(J1 to J4 are all common on the BIC10.)
Note: Remove and discard any resistors that are blocking access to J5 connection point on BLJ2/3 board. Set the J11
RS485 termination jumper to the 2 - 3 position in the BIC 10 of the last cabinet in the system.
Figure 6 - 7: BIC 10 Intercabinet Alarm and Serial Bus Wiring
Intercabinet Alarm and Serial Bus Connections (continued)