Battery Connection Panel Options (continued )
Figure 10-3: H569-4827 Battery Connection Panel Options
ED83143-31 G31/43
(1) 1200A LVBD G31
(2) NH3 DIN each G31
(2) 600A Shunt each G43
ED83143-31 G45 with G36
6000A Battery Shunt included in all GPS
4827 configurations
Connecting (+) and (-) Conductors
-48volt Systems
Battery (-) conductors are connected to the exposed bus bar ends of the battery fuse holders,
contactors, or shunt. Battery (+) conductors are connected to the battery return bus. See Figures 10-2
and 10-3 to locate the battery connection panels and battery return bus. Also see Figures 4 and H3 in
the T83314-30 drawing for additional information.