EasyManua.ls Logo

ABB Galaxy Power System - Ground Terminal Strip in Distribution-only Cabinets

ABB Galaxy Power System
147 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 43
© Copyright 2021 ABB. All rights reserved.
Centralized Architecture (Continued)
Ground Terminal Strip in 4800A GPS Distribution-only Cabinets
4800A GPS Distribution-only cabinets (H569 - 434 G429, G430; H569 - 4830 G429, G430) do not have
any internal return buses, so the return circuits for the BIC (Bay Interface Card) and controller, mounted
on the cabinet door, are wired to a ground terminal strip (848474185)mounted off a standoff on either
the rear wall (standard width J85582C1 L3) or the left side of the top front panel (wide width J85582C1
L103) as indicated below:
In order for the BIC or M2 to be powered in these cabinets, a 12 ga return lead must be extended from
the external plant return bus to this ground terminal strip.
J85582C1 L10
WIDE BAY 4800A DISTRIBUTION ONLY CABINET
Wiring from
BIC/M2 or
other cabinet
equipment

Table of Contents