AC
Panel Suffix
Cabling Arrangement
AC Battery and DC Load
Through bottom of cabinet Through bottom of cabinet
B Through bottom of cabinet Through top of cabinet
C Through top of cabinet Through bottom of cabinet
Figure 7-22: Bottom Cable Feed Option for GPS4848/100
Bottom Cable Feed Options for GPS 4848/100 Systems
Standard cabinets are designed so that AC, battery, and DC load cables are routed through the top of
the cabinet, as a top-feed system, However, cabinets, using the ED83142-30 G26 AC panel, can also, be
configured as a bottom-feed system, with the cabling routed through the bottom of the cabinet (See
Figure 7-22). For the AC inputs from the bottom of the cabinet, this panel has a 2-inch diameter hole in
the back of its chassis to accept a 90° conduit fitting. Suffixes added to the “G26” indicate the cabling
arrangements as listed below: