Torque Settings for Hardware
Table 3-A: Torque Settings for Hardware
Unpacking - Location
Before continuing, verify that the following conditions exist at the installation site:
· Floor is conditioned and clean (refers to removal of any combustible flooring, e.g., carpet, wood, etc.)
· Batteries and associated stands are in place.
· Cable rack not supported by cabinets is in place.
· Job Site Documentation is available that details cabinet locations, dc distribution assignments, and
Remote Peripheral Monitoring System module location and assignment.
Metric
Screw Size Torque (N·m) Torque (in·lbs)
M2 0.24 2
M2.5 0.48 4
M3 0.9 8
M3.5 1.4 12
M4 2 18
M5 4 35
M6 7 62
M8 18 145
M10 34 300
M12 58 513
English
Screw Size Torque (N·m) Torque (in·lbs)
6 - 32 1.1 10
8 - 32 2.3 20
10 - 32 2.8 25
12 - 24 4 35
1/4 - 20 7 65
5/16 - 18 15 135
3/8 - 16 27 240