BLJ2/3 to BIC11 or BIC11 to BIC11 (Millennium II Controller)
The cable used in this procedure is:
Rectifier Interface Cable Assembly 847690799 (10 feet) (provided with cabinet)
Refer to Figure 6 - 8 for this procedure.
BLJ2/3 to BIC11 or BIC11 to BIC11 (Millennium II Controller)
Step Action
Connect the Rectifier Interface Cable Assembly from J5 of one BLJ2/3 board to any J1 - J4 of the BIC11 board in the
next cabinet or from any of J1 to J4 of one BIC11 to any of J1 to J4 of the next BIC11.
(J1 to J4 are all common on the BIC11.)
Note: Remove and discard any resistors that are blocking access to J5 connection point on BLJ2/3 board. Set the
J13 RS485 termination jumper to the 2 - 3 position in the BIC11 of the last cabinet in the system.
Figure 6 - 8: BIC11 Intercabinet Alarm and Serial Bus Wiring