Distribution Panels
ED83143-31 Group 1
Large Circuit Breaker Kits
for Groups 1, 4, 101, and 104
Comcode
Size
(A)
Breaker
Positions
Wire Ga
(min)
108908187 125 1 2
108908179 150 1 1/0
108908195 175 1 2/0
108908203 225 1 4/0
108908211 300 2 (2) 4/0*
108908237 400 2 (2) 4/0*
108908229 500 3 (3) 4/0*
108908252 600 3 (3) 4/0*
108984782 800 4 (4) 4/0*
*Cables must be the same length and terminate at a
common at each end.
Lugs and Hardware
Lug
Comcode
Type
Std Wire
Ga
(Class B)
Flex Wire
Ga
(Class I)
Metric
Wire Size
(mm
2
)
Hardware
Kit
(Grade 2)
For 1, 2, or 3-position breakers (double-hole load and return lugs)
406338665
load 2 -- 35
847867132
rtn 2 -- 35
405348228
load 1/0 -- 50
rtn 1/0 -- 50
405348236
load 2/0 1/0 70
rtn 2/0 1/0 70
406021725
load -- 2/0 --
rtn -- 2/0 --
405348251
load 4/0 -- --
rtn 4/0 -- --
405347923
load -- 4/0 120
rtn -- 4/0 120
Note
Jumper straps (J1 to J3) on the CLR card shall
be left in the factory default 5 - 12 position for
use with ABB Power Shunt RPM monitoring.
Move these jumper straps to the “Bypass” 1 - 8
position to permit shunt monitoring with non-
ABB equipment. Protection for this wiring
must be provided by the user when these
current-limiting resistors are bypassed.
Figure 8-2: ED83143-31 Group 1 (H469-434/4827/4830 G43/A, G101/A, G102/A, G103/A, or G104/A)
1200A (800A e/w LVLD) DC Distribution Panel
To DC Loads
847867132 Bolt Kit
Torque to 300 in-lbs (34 Nm)
6 Positions for Large
U.S. Circuit Breakers
Alarm Card
12” REF
(305mm)
Connects to
Charge Return Bus
12” REF
(305mm)
Terminal Card (See Note and CLR Card Assignment View)