Page 53
© Copyright 2021 ABB. All rights reserved.
Millennium II Controller Configuration of BIC Shunt Channels
Software Configured Bay Current Shunt Channel Configuration in Millennium II
Bay Shunt Channels that have been set to “Software Configured” (BLJ2/3) or “CONFIG” (BIC9, BIC 10
and BIC11) setting must be then set to the desired configuration for the shunt size and type within the
Millennium II controller itself, by logging in over the web pages.
1. Go to the Settings > Programming >Monitor Channels screen. Click on “Monitor Channels”.
2. Choose the “Bay Current Monitor” item from the pull-down menu.
3. All BIC Current inputs should be listed. Those with current values (including zero) are installed and
active. The BIC current monitoring channels are identified by “BCMxxyy” where “xx” is the input
channel number and “yy” is the ID number set for the BIC.