Millennium II Controller Configuration of BIC Shunt Channels (continued)
4. Select the “Click to Update” button of the appropriate BIC Shunt channel. A separate pop-up menu
specific for the selected input will appear for editing.
5. Edit/verify all appropriate configuration settings which include:
· Shunt Current and Voltage values.
· Shunt Type
· Shunt Type will typically be set to “Battery” if the assigned shunt is measuring Battery
string charge (-) or discharge (+) current in a distributed architecture plant.
· Shunt Type will be set to “Load” (shown above) only when using the ED83311-30 overhead
bus arrangements with Distribution-only cabinets each fed by their own shunt. When this is
the case, Shunt Type for Plant Current & Plant Shunt 2 Current on the Settings -> Shunts
web page (below) must both be set to None and the “Total System Load Monitored by Re-
mote Shunts” checkbox there must be selected.
· Click the “Submit Channel” button to ensure all changes are saved.
· Repeat for all BIC monitored software configured Shunt channels.
Set both to
NONE