Cabinet Installation (continued)
Note: Facia Cover installation is optional.
Figure 5 - 4: Fascia cover installation
Figure 5 - 5: Air inlet cover installation
847833340 Cover (Air inlet) Or CC848924126
Cover (Air inlet) H569434G430 only
Note: Install the Air inlet cover shipped with
each GPS4848/100 cabinet after
shimming and securing the cabinet to
the floor
Note: Shown here is multi-cabinet installation.
For single cabinet installation, ignore the
side by side illustration.
Shims under cabinet to level
Shims provided
842439861 (0.063”)
842439879 (0.125”)
842439887 (0.25”)
Secure Cabinet to floor or Bat-
tery stand
Four corners for seismic zones
3 and 4. Two opposite corners
for zones 0, 1, and 2.
Threaded Rod 5/8”
847837879 Fascia cover
or 84285854 RPM Fascia cover
901015461 (4) Nuts 8-32
Left End of line - up only (optional)
Single cabinet or cabinet
at Left End of line - up only
Fascia cover
847837879 - GPS4848/100
848513594 - GPS2424/30,
GPS4812/24
901015461 (4) Nuts 8-32
Right End of line - up only
(optional)
847891264 adapter to 5/8”
threaded rod to be used if
cable rack is supported from
cabinet. Otherwise, use M10
hardware provided to secure
brackets to cabinet and dis-
card adapters.
Secure cabinet together
Hardware provided:
901263327 Screw M8 x 25mm
901249821 Lock washer M8
901249813 Flat washer M8
901249839 Hex Nut M8
(2 Places each)
Single cabinet or cabinet
at right End of line - up only
847704913 Bracket (typical)
Hardware Provided:
901284562 Screw M10 X 35mm
901284554 Loak washer M10
901284547 Flat washer M10
Note bracket orientation