Page 9
© Copyright 2021 ABB. All rights reserved.
Safety Statements (continued)
· Circuit Breakers and Fuses: Installing fuses or circuit breakers not specified for use in this
equipment may result in injury to service personnel or equipment damage.
· Fuses/circuit breakers may not be provided with the equipment. Refer to the Galaxy Power
System documentation for the proper hardware. Use only those specified in the equipment
ordering guide.
· Size as required by the National Electric Code (NEC) and/or local codes. Safety Tested Limits
- Refer to the equipment ratings to assure current does not exceed: Maximum Load – 80% of
protector rating.
· GMT Style Fuses – Use only fuses provided with safety caps.
· Compression Connectors – For installations in the U. S. or Canada, use Listed/Certified
compression connectors to terminate Listed/Certified field-wire conductors where required. For all
installations, apply the appropriate connector to the correct size conductor as specified by the
connector manufacturer, using only the connector manufacturer’s recommended tooling or tooling
approved for that connector. If the proper connector for the country of installation is not provided,
obtain appropriate connectors and follow manufacturer’s and all local requirements for proper
connections.
· Battery input cables must be dressed to avoid damage to the conductors (caused by routing
around sharp edges or routing in areas where wires could get pinched) and undue stress on the
connectors.
· Field-wired Conductors - Follow all National Electric Code (NEC) and local rules and regulations.
· Select wire insulation rated for a minimum of 90°C. Select wire size using NEC ampacity
table for AC field-wiring conductors rated for 75°C.
· Select DC filed-wiring conductors using NEC ampacity table for 90°C ampacity that are
equal to or greater than the circuit breaker/fuse rating.
· Provide an accessible AC and DC disconnect/protection device to remove input power from the
equipment in the event of an emergency. This device must open all poles and be connected
together. When connecting to 3-wire plus neutral supply systems, the neutral must be readily
earthed at the supply, i.e., this equipment is not intended to be connected to IT supply systems.
· Alarm Signals – Provide external current limiting protection. Rating 60V, 0.5A unless otherwise
noted.
· Grounding – Connect the equipment chassis directly to ground. In enclosed equipment cabinets
connect to the cabinet AC service ground bus. In huts, vaults, and central offices connect to the
system bonding network.