Commissioning
FCA/S 1.x.x.1 | 2CDC508134D0202 193
Send output value
Options:
On request
On change
Cyclically
On change and cyclically
This parameter defines how the output value should be sent.
On request: The output value is sent on request.
The Request output value Input a communication object appears.
As soon as a 1 is received at this communication object, the current output value is sent once to the
communication object Output value Input a.
On change: The output value is sent when a change occurs.
Cyclically: The output value is sent cyclically.
On change and cyclically: The output value is sent cyclically when a change occurs.
Selection of options On change, cyclically and On change and cyclically:
Dependent parameters:
Output value is sent from a
change of [x 0.1 °C]
Options:
1…10...200
This parameter defines from which temperature change the output value should be sent.
10: The output value is sent after a change of 1 °C.
Output value is sent
Options:
Every second
Every 2/3/5/10/30/60 seconds
Every 2/3/5/10/30/60 minutes
Every 2/3/5/10/12 hours
The interval for cyclical sending is set with this additional parameter.