54 | NGC8200 AND PGC1000 USER MANUAL | 2101510MNAH
Figure 6-15: IP configuration for host system (automatic addressing)
6.3.3.3 Set up PCCU32 and connect
This procedure assumes that the default Ethernet configuration is intact. The analyzer has a default IP
address assigned at the factory (169.254.0.11).
To configure PCCU32 for TCP/IP communication:
1. Connect an Ethernet cross-over cable between the PC and analyzer. Make sure the PC or laptop
is powered on.
2. Power on the analyzer. Diagnostic tests begin immediately. See section 6.4 Power on sequence
for details.
3. Launch PCCU32.
4. Click Setup on the PCCU32 toolbar menu.
Figure 6-16: PCCU32 Setup
5. On the System Setup tab, under PCCU Connect Method, click TCP/IP (Figure 6-17).
6. Type the default IP address (169.254.0.11) into Network ID or IP field.