EasyManua.ls Logo

ABB PQFS

ABB PQFS
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
204 Troubleshooting guide Manual Power Quality Filter PQFS
Verify the fuses (PF1 and
PF2) and the resistors (R1
and R2) of the preload
circuit (A001).
Inspect the DC-bus for
traces of damage that
may have caused a short
circuit on the DC-side of
the IGBT-module or on
the DC voltage
measurement board.
Several units same id
Two or more units in a
filter system have the
same CAN_ID.
Check the CAN_ID of the
different units in the set
of filters: each unit has to
have one unique CAN_ID
on the DIP switch S5-1 to
S5-3.
Reset the filter by
switching off and on the
power. If the problem
persists, contact your
ABB representative. The
controller card must
probably be replaced.

Table of Contents

Related product manuals