EasyManua.ls Logo

ABB PQFS

ABB PQFS
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual Power Quality Filter PQFS Technical specifications 213
Can be used to monitor the filter state (e.g. filter on/off or
specific filter warnings/alarms) and the network state.
Alarm contact 1 universal alarm contact with two complimentary outputs
(NO/NC) on PQF-Manager. Triggered by any fault.
Maximum continuous rating: 250 Vac/1.5 A
Filter losses
Typical values
Maximum values
Unit rating: 30 A
0.7 kW
1.5 kW
Unit rating: 45 A 1 kW
1.8 kW
Unit rating: 60 A 1.3 kW
2.1 kW
Unit rating: 70 A
1.8 kW
2.6 kW
Unit rating: 80 A 2.1 kW
2.9 kW
Unit rating: 90 A
2.4 kW
3.2 kW
Unit rating: 100 A 2.7 kW
3.5 kW
Unit rating: 120 A 3.5 kW
4.3 kW
Phase to earth resistance
1.67 M/filter unit
Noise intensity 30A - 60A: 65.3 dBA typically
70A - 100A: 68.4 dBA typically
120A : 70.9 dBA typically
Communication
Through PQF-Manager display.
Through Modbus RTU (with optional RS485 Modbus
Adapter).
Through Modbus TCP (with Ethernet).
Through dedicated optional software PQ-link (with USB-
Ethernet).
Programming Through PQF-Manager display.
Through USB-Ethernet with dedicated optional software
(PQ-Link).
Fuse information
Main circuit fuses Not included
Auxiliary circuit fuses French Ferrule 10 x 38 gG/gl, 6A, 500V, Isc ~120kA
Main options
PQ-Link software
RS-485 Modbus adapter
Easy connection box for power cables
Cable extension kit for PQF-Manager
Remark:
(a)
Under exceptional circumstances other limits may be reached before the RMS current limit (e.g.
temperature limit, peak current limit, peak voltage limit).

Table of Contents