Manual Power Quality Filter PQFS  Electrical design and installation 41
WARNING: Consult your cable manufacturer for the applicable cable manufacturer
data.
Table 19: Allowed cable current for different cable sections noting the skin effect and typical
cable manufacturer data – Network frequency 50Hz
parallel
cables
due to
paralleling
current
[Arms]
factor
current
[Arms]
current
[Arms]
factor
current
[Arms]
16 6 1 1 100
0.997
100 75
0.999
75
25 4 1 1 130
0.993
125 100
0.997
100
35 2 1 1 160
158 120
119
50
1-1/0
1 1
0.975
185 145
0.989
142
70 2/0 1 1 230
0.955
220 180
0.98
176
95 3/0 1 1 285
0.93
265 220
0.965
210
120 4/0 1 1 325
290 250
238
150 300MCM 1 1 365
320 285
265
185 350MCM 1 1 415
0.844
350 325
0.908
295
240 500MCM 1 1 495
390 385
335
300 600MCM 1 1 550
420 425
358
16 6 2 0.8 160
0.997
159 120
0.999
120
25 4 2 0.8 208
205 160
160
35 2 2 0.8 256
250 192
190
50 1-1/0 2 0.8 304
0.975
290 232
0.989
229
70 2/0 2 0.8 368
350 288
282
95 3/0 2 0.8 456
420 352
340
120 4/0 2 0.8 520
0.904
470 400
0.95
380
150 300MCM 2 0.8 584
510 456
424
185 350MCM 2 0.8 664
560 520
472
240 500MCM 2 0.8 792
0.804
630 616
0.876
540
300 600MCM 2 0.8 880
675 680
573
Remark: The highlighted values in Table 19 refer to cable sizes that correspond to typical
filter ratings. Note that in 4-wire systems, the neutral may have to carry up to 3 times