Functions
Chapter 10
142
1SFC132003M0201
10:21 Overload protection, type of
operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Protections/Overload/OL Op
This parameter makes it possible to select between three
different actions by the softstarter when the protection is
activated. It is active only if the motor overload protection is
selected.
Stop–M The motor stops and a manual reset is required
before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears
(motor temp. <80%)
Ind The motor continues to run but a fault indication
is given.
Parameter
text
Default value Setting range Description
OL Op Stop–M Stop–M, Stop–A,
Ind
Type of opera-
tion for over-
load protection