Settings and configuration
Chapter 7
106
1SFC132003M0201
7:2.4.7 Outputs
To set parameters related to the programmable outputs,
enter the Outputs group.
Output relay K4 (Relay K4)
Select the required function for the output relay K4.
One of the following functions can be selected:
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s) where following
functions can be selected individually:
Overload protection
•Fault
High current protection
Thyristor overload protection
Locked rotor protection
Underload protection
Phase imbalance protection
PTC protection
Phase reversal protection
Overload warning
Thyristor overload warning
High current warning
Low current warning
Shunt Fault
Press Store to save/activate the selected function.
Output relay K5 (Relay K5)
Select the required function for the output relay K5.
One of the following functions can be selected:
Run Run indication.
TOR Top of ramp indication.
Event Indication of selected event(s), see relay K4.
Press Store to save/activate the selected function.
Functional Settings
Start/Stop
Protections
Warnings
Inputs
Faults
Outputs
Fieldbus
Settings
Seq Start
Figure 32: Outputs groups
Torque control
Analog Output