7:2.4.6 Inputs
To set parameters related to the programmable inputs, enter
the Inputs group.
First programmable input (In0)
Select the required function for the input In0.
Press Store to save/activate the selected function.
One of the following functions can be selected:
None No specific function (not activated).
Reset Reset of an event.
Enable When In0=0 the softstarter stops immediately.
When In0=1 the softstarter is in normal
operation.
Overrides all other inputs, except
LOCAL CONTROL.
Jog Performs a start ramp until command is
released, then the motor stops immediately.
DOL Open/close of the by-pass contactor
(PSTB370...PSTB1050).
Only if Setting I
e
is equal or lower than AC-3
rating.
Start2 Start signal for 2nd parameter set-up.
FB-Dis Disable of the fieldbus communication. The
softstarter can be controlled by the hard wire
inputs instead.
Press Store to save/activate the selected function.
Caution!
The motor may start unexpectedly if there is a start signal
present when doing any of the actions listed below.
Switching from one type of control to another (fieldbus
control / hardwire control)
Re-programming of the programmable inputs
Reset all Settings (programmable input set to Enable)
Start/Stop
Protections
Warnings
Inputs
Faults
Outputs
Fieldbus
F
igure 31: Inputs groups
Seq Start
Settings
Functional Settings
Torque control
Analog Output