Functions
Chapter 10
138
1SFC132003M0201
10:12 Kick start
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Start
In some applications it can be necessary to kick loose the
motor i.e. initial friction, and therefore a kick start can be
used. With this function a selectable fix voltage is applied
during a settable time. Note that the current limit function is
not working during kick start.
10:13 Kick start level
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Level
With this parameter it is possible to set the level of the kick
start. It is active only if kick start is selected.
10:14 Kick start time
Path in menu:
Menu/SETTINGS/Functional Settings/
Start/Stop / Kick Time
This parameter makes it possible to set the time of the kick
start. It is active only if kick start is selected.
1SFC132101F0001
F
igure 12: Kick start
Parameter
text
Default value Setting range Description
Kick Start No Yes, No Selection of Kick
Start
Parameter
text
Default value Setting range Description
Kick Level 50% 50...100% Level of Kick
Start
Parameter
text
Default value Setting range Description
Kick Time 0.2 s 0.1...1.5 s Time for Kick Start