10:73 Setting current, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./2nd Set Ie
This parameter makes it possible to set the rated motor
current for the second parameter set.
10:74 Start ramp, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Start Ramp3
This parameter makes it possible to set the start ramp time
for the third parameter set.
10:75 Initial voltage, third sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/3rd Seq. Param./Init Volt3
This parameter makes it possible to set the initial voltage for
the third parameter set.
Parameter
text
Default value Setting range Description
2nd Set Ie Ir 9...1207A divided
into 19 overlap-
ping ranges
Second
sequence, motor
rated current
Parameter
text
Default value Setting range Description
Start
Ramp3
10 s 1...30s, 1...120s Third sequence,
time for start
ramp
Parameter
text
Default value Setting range Description
Init Volt3 30% 30...70% Third sequence,
initial voltage for
start ramp