Functions
Chapter 10
166
1SFC132003M0201
10:63 Fieldbus address
Path in menu:
Menu/SETTINGS/Functional Settings/
Fieldbus/Fieldb Addr
With this parameter it is possible to set a fieldbus address for
the softstarter. Select a suitable, not occupied number as the
address.
10:64 Fieldbus auto disable
Path in menu:
Menu/SETTINGS/Functional Settings/
Fieldbus/FB Auto Dis
This parameter enables the function fieldbus auto disable.
With this function enabled, the control of the softstarter will
automatically switch over from the fieldbus to the hard wire
inputs if the fieldbus malfunctions for instance due to power
loss or broken cable. When the fieldbus starts working again
the control is automatically switched back to the fieldbus.
Caution!
The motor may start unexpectedly if there is a start signal
present when doing any of the actions listed below.
Switching from one type of control to another (fieldbus
control / hardwire control). Remember that when Field-
bus auto disable is active, this switch can be done auto-
matically.
Re-programming of the programmable inputs
Reset all Settings (programmable input set to Enable)
Parameter
text
Default value Setting range Description
Fieldb Addr 0 0...1000 Fieldbus
address
Parameter
text
Default value Setting range Description
FB Auto
Dis
No Yes, No Enable fieldbus
auto disable