EasyManua.ls Logo

ABB PST210 - Current Limit, Second Sequence; Initial Voltage, Second Sequence; Start Ramp, Second Sequence

ABB PST210
200 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
Chapter 10
169
1SFC132003M0201
10:70 Start ramp, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Start Ramp2
This parameter makes it possible to set the start ramp time
for the second parameter set.
10:71 Initial voltage, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Init Volt2
This parameter makes it possible to set the initial voltage for
the second parameter set.
10:72 Current limit, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Curr Lim2
This parameter makes it possible to set the current limit level
for the second parameter set.
Parameter
text
Default value Setting range Description
Start
Ramp2
10 s 1...30s, 1...120s Second
sequence, time
for start ramp
Parameter
text
Default value Setting range Description
Init Volt2 30% 30...70% Second
sequence, ini-
tial voltage for
start ramp
Parameter
text
Default value Setting range Description
Curr Lim2 4 x I
e
2.0...7.0 x I
e
Second
sequence, cur-
rent limit

Table of Contents