10:43 Low current warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn I=Low/Wa I=L Lev
This parameter makes it possible to set the indication level of
the low current warning function.
10:44 Overload warning
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn OL
If the function is selected a warning signal will be given that
the overload protection will be activated, if the motor load
does not decrease.
10:45 Overload warning level
Path in menu:
Menu/SETTINGS/Functional Settings/
Warnings/Warn OL/Wa OL Lev
This parameter makes it possible to set the indication level of
the motor overload protection. The actual trip level of the
protection is represented by 100%.
Parameter
text
Default value Setting range Description
Wa I = L Lev 0.8 x I
e
0.4...1.0 x I
e
Trip level for
low current
warning
Parameter
text
Default value Setting range Description
Warn OL No Yes, No Overload warning
Parameter
text
Default value Setting range Description
Wa OL Lev 90% 40...99% Trip level for
overload warning