Trouble shooting
Chapter 11
185
1SFC132003M0201
11:6 Protection indication
Status Possible cause Solution
Overload protection
The motor has been exposed to
an overload condition because
the current over a certain time is
too high.
(The load on the motor shaft is
too high)
In Line
At start
Check and correct the reason for the
overload. Check that current limit level is
not set too low.
Check that the ramp time for start is not
too long.
Check that correct overload class is
used.
Check that parameter Setting Ie is cor-
rect.
Continuous run
Check and correct the reason for the
overload.
Inside Delta
At start
Check and correct the reason for the
overload.
Check that current limit level is not set
too low.
Check that the ramp time for start is not
too long.
Check that correct overload class is
used.
Check that parameter Setting Ie is set to
58% ( ) of the rated motor cur-
rent.
Continuous run
Check and correct the reason for the
overload
Power on ProtectionFault
Prot Motor OL
Reset Back
13()