Trouble shooting
Chapter 11
186
1SFC132003M0201
Underload protection
The motor current is below set
level and time.
Check and correct the reason for the
underload.
Check that the settings are according to
the operation conditions.
Locked rotor protection
The motor is running stiff by
some reason.
A damaged bearing or a stucked
load could be possible causes.
Check the bearings of the motor and
load.
Check that the load is not running stiff.
High current protection
A fault current, higher than 8
times the softstarter ratings, has
occurred.
Check the circuits including the motor for
any insulation fault phase to phase or
earth fault.
Phase imbalance protection
Unbalance in the phase currents. Check the main voltage and the motor
circuit.
Restart the motor and check the phase
currents
Phase reversal protection
The phase sequence is not
correct.
Change the phase sequence on the line
side to (L1-L2-L3).
Status Possible cause Solution
Power on ProtectionFault
Prot Underload
Reset Back
Power on ProtectionFault
Prot Locked Rot
Reset Back
Power on ProtectionFault
Prot High I
Reset Back
Power on ProtectionFault
Prot Phase Imb.
Reset Back
Power on ProtectionFault
Prot Phase Rev
Reset Back