10:51 Thyristor short circuit fault, type of
operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/SCR SC Op
If one or several thyristors are shorted, this parameter makes
it possible to select between two different actions of the
softstarter.
Stop–M The motor stops and a manual reset is required
before restart.
Stop–A The motor stops and an automatic reset is
performed when the fault disappears.
10:52 By-pass doesn't open fault,
type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/Faults/
BP Closed Op
This parameter makes it possible to select between two
different actions of the softstarter if the by-pass contactor
does not open in a proper way.
Stop-M The motor stops and a manual reset is required
before restart.
Stop-A The motor stops and an automatic reset is
performed when the fault disappears.
Parameter
text
Default value Setting range Description
SCR SC
Op
Stop–M Stop–M, Stop–A Type of opera-
tion for thyristor
short circuit fault
Parameter
text
Default value Setting range Description
BP Closed
Op
Stop-M Stop-M, Stop-A Type of opera-
tion if the by-
pass does not
open

Table of Contents