Connection
Chapter 5
44
1SFC132003M0201
When used for marine applications, please use standard
installation cables with concentric conductors for earth. This
earth conductor shall be 360 degree connected to earth in
the cable glands or in the near of the gland.
Warning!
Capacitors for power factor compensation are not allowed
in between the softstarter and the motor, since this can
cause current peaks which can burn the thyristors in the
softstarter. If such capacitors are to be used, they should be
connected on the line side of the softstarter.
1L1
3L2
5L3
1
100-250V
Stop
Start
In0
In1
Vc
50/60 Hz
2
3
4
5
6
7
8
9
10
Vp
Vp
11
K4
12
13
14
Vn
15
16
K5
17
18
19
K6
20
LISTED 7F39
IND. CONT. EQ
.
1SFA 894 007 R1002
IEC 947-4-2
Ie: 37-72A
Us: 100-250V AC/DC
UL 508
Uc: 100-250V AC/DC
FLA: 37-68A
Made in Sweden
Ue: 220-230 380-400 500 V
72: AC-53a: 8-1.6: 80-6
In line 18,5 37 45 kW
Ue 208 220-240 440-480 V
PTC
Key-Pad
FELDBUSS
CAUTION
Fuse 250A TYPOWER ZILOX
Max short circuit current 65kA at 480V
Wire 1-8 Al Cu 75C only, 35lb-in
Overload Capacity 115% of Continuous
LISTED 7F39
IND. CONT. EQ
.
1SFA 894 007 R1002
IEC 947-4-2
Ie: 37-72A
Us: 100-250V AC/DC
UL 508
Uc: 100-250V AC/DC
FLA: 37-68A
Made in Sweden
Ue: 220-230 380-400 500 V
72: AC-53a: 8-1.6: 80-6
In line 18,5 37 45 kW
Ue 208 220-240 440-480 V
In line 20 20 50 Hp
CAUTION
Fuse 250A TYPOWER ZILOX
Max short circuit current 65kA at 480V
Wire 1-8 Al Cu 75C only, 35lb-in
Overload Capacity 115% of Continuous
PTC
Key-Pad
FIELDBUS
2T1
4T2
6T3
1SFC132048F0001
Figure 3: Connection of line side and motor side
Motor side
Line side