EasyManua.ls Logo

ABB REB670 Series - CT disconnection for bus interconnector CT cores

ABB REB670 Series
476 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
included to the differential zone A when input signal CTRLZA on corresponding bay block
is given logical value one and it will be excluded from the differential zone A when input
signal CTRLZA on corresponding bay block is given logical value zero.
included to the differential zone B when input signal CTRLZB on corresponding bay block
is given logical value one and it will be excluded from the differential zone B when input
signal CTRLZB on corresponding bay block is given logical value zero.
This setting is typically used for feeder bays in double busbar stations in order to form proper
busbar disconnector replica. It is especially suitable both when normally open and normally
closed (that is, "a" and "b" contacts) auxiliary contacts from the busbar disconnectors are
available to the IED.
If for a particular CT input setting parameter
ZoneSel
is set to
Ctrl_Excludes
, then this CT input
will be:
excluded from the differential zone A when input signal CTRLZA on corresponding bay
block is given logical value one and it will be included to the differential zone A when input
signal CTRLZA on corresponding bay block is given logical value zero
excluded from the differential zone B when input signal CTRLZB on corresponding bay
block is given logical value one and it will be included to the differential zone B when input
signal CTRLZB on corresponding bay block is given logical value zero.
This setting is typically used for feeder bays in double busbar single breaker stations in order
to form proper busbar disconnector replica. It is especially suitable when only normally closed
(that is, “b” contact) auxiliary contact from the busbar disconnector(s) is available to the IED.
For more information please refer to Figure
63.
6.1.3.6 CT disconnection for bus interconnector CT cores
M12113-3 v4
For simplicity purpose, sometimes we also refer to a bus-section or bus-coupler bay as a bus
interconnector bay. In practice there are three different solutions for bus interconnector bay
layout. First solution is with two sets of main CTs, which are located on both sides of the
circuit breaker, as shown in Figure
45.
ZA
21 8
ZB
21 8
BS
en01000013.vsd
IEC01000013 V1 EN-US
Figure 45: Example of station with two sets of main CTs in the bus-section bay
Two differential zones are overlapping across the bus-section or bus-coupler circuit breaker.
All faults in the overlapping zone will be instantly tripped by both zones irrespective of the
section/coupler circuit breaker status. However with modern busbar protection it is possible
to disconnect both CTs from the relevant zones when the bus-section or bus-coupler circuit
Section 6 1MRK 505 370-UEN D
Differential protection
102 Busbar protection REB670
Application manual

Table of Contents

Related product manuals