REB670(B20-X01) /REB670(B21-X01) / REB670(B31-X01)
PHASE L3
REB670(B20-X01) /REB670(B21-X01) / REB670(B31-X01)
PHASE L2
REB670(B20-X01) /REB670(B21-X01) / REB670(B31-X01)
PHASE L1
ZA
ZB
QA1
QB1
QA1
QB1
QA1
QB1
QA1
QB1
HW LOGIC
AC LOGIC
BUS PTRC
87B Id/I
BUS PTRC
87B Id/I
BZNS PDIF
87B Id/I
BUS PTRC
87B Id/I
BZNS PDIF
87B Id/I
QB1 QB2
QA1
BCZS PDIF
87B Id/I
BZIS GGIO
87B Id/I
C MMXU
MET I
DRP RDRE
DFR/SER DR
VERSION OF REB670
NUMBER OF FEDERS IN
BOTH BUSBAR SECTIONS
REB670(B20 – X01) 1-Phase, 12 Bays, 2 Zones for Simple
Station Layout 12 AI
11*
REB670(B21 – X01) 1-Phase, 12 Bays, 2 Zones for Simple
Station Layout 12 AI
11*
* With Just one CT in the Bus Section Bay
NUMBER OF REB670
REQUIRED BY THE SCHEME
3
3
REB670(B31 – X01) 1-Phase, 24 Bays, 2 Zones for Simple
Station Layout 24 AI
23* 3
C MMXU
MET I
C MMXU
MET I
NUMBER OF FEEDERS IN
BOTH BUSBAR SECTIONS
IEC13000224-3-en.vsd
Optional Functions
PH4S PTOC
51 I>
CCS RBRF
50BF I>BF
SMB RREC
79
5(0->1)
Other Functions available from the function library
BDC GAPC
87B
Q CBAY
Control
C MSQI
MET Isqi
VN MMXU
MET UN
S SIML
71
S SIMG
63
S XCBR
3 Control
S SCBR
Control
V MMXU
MET U
V MSQI
MET Usqi
ETP MMTR
MET
W/Varh
CV MMXN
MET P/Q
DELI SPVC
7I
DELTAI
DELV SPVC
7V_78V
DELTAU
DEL SPVC
7
DELTA
CHM MHAI
ITHD ITHD
VHM MHAI
VTHD UTHD
IEC13000224 V3 EN-US
Figure 9: Configuration diagram for B21, configuration X01
3.1.8 Description of 1 ph package B31
SEMOD129275-58 v8
One-phase version of the IED with two low-impedance differential protection zones and
twenty-four CT inputs B31.
• The IED is intended for busbar protection applications in big substations where dynamic
Zone Selection, quite large number of binary inputs and outputs and many CT inputs are
needed. The IED includes two differential zones and twenty-four CT inputs. Note that
binary inputs can be shared between phases by including the LDCM communication
module. This simplifies panel wiring and saves IO boards.
Section 3 1MRK 505 370-UEN D
Configuration
54 Busbar protection REB670
Application manual