EnaAbs
: This setting is used to select the comparison type between signed and absolute
values.
•
Absolute
: Comparison is performed on absolute values of input and reference values
•
Signed
: Comparison is performed on signed values of input and reference values.
RefSource
: This setting is used to select the reference source between input and setting for
comparison.
•
Input REF
: The function will take reference value from input REF
•
Set Value
: The function will take reference value from setting
SetValue
SetValue
: This setting is used to set the reference value for comparison when setting
RefSource
is selected as
SetValue
.
13.13.4 Setting example
GUID-13302FD6-1585-42FE-BD6D-44F231982C59 v2
For absolute comparison between inputs:
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Input REF
Similarly for Signed comparison between inputs
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Input REF
For absolute comparison between input and setting
Set the
EnaAbs
=
Absolute
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
Similarly for signed comparison between input and setting
Set the
EnaAbs
=
Signed
Set the
RefSource
=
Set Value
SetValue
shall be set between -2000000000 to 2000000000
13.14 Comparator for real inputs - REALCOMP
13.14.1 Identification
GUID-0D68E846-5A15-4C2C-91A2-F81A74034E81 v1
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Comparator for real inputs REALCOMP Real<=>