IEC13000016 V2 EN-US
Figure 140: APC - Local remote function block
12.3.3 Switch controller SCSWI
M16596-3 v6
SCSWI may handle and operate on one three-phase device or three one-phase switching
devices.
After the selection of an apparatus and before the execution, the switch controller performs
the following checks and actions:
• A request initiates to reserve other bays to prevent simultaneous operation.
• Actual position inputs for interlocking information are read and evaluated if the operation
is permitted.
• The synchrocheck/synchronizing conditions are read and checked, and performs
operation upon positive response.
• The blocking conditions are evaluated
• The position indications are evaluated according to given command and its requested
direction (open or closed).
The command sequence is supervised regarding the time between:
• Select and execute.
• Select and until the reservation is granted.
• Execute and the final end position of the apparatus.
• Execute and valid close conditions from the synchrocheck.
At error the command sequence is cancelled.
1MRK 505 370-UEN D Section 12
Control
Busbar protection REB670 289
Application manual