Harm3Level
: This is the set level of 3
rd
harmonic with respect to fundamental signal at which
the
DelI>
should be modified. Typical setting is 15% of fundamental signal.
StValGrad
: This setting is used to modify the
DelI>
based on 3
rd
harmonic level. Typical setting
is 10% to modify the
DelI>
.
11.5 Delta supervision of real input DELSPVC
GUID-470F7470-F3D1-46BC-B0EA-CD180FBA0AB2 v1
11.5.1 Identification
GUID-66CFBA71-B3A4-489F-B7F4-F1909B75E1DD v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Delta supervision of real input DELSPVC – –
11.5.2 Application
GUID-C7F56ACE-D1F2-4F33-96CA-108D7F11FDD5 v1
Delta supervision of real input DELSPVC is a general processed input delta supervision. It is
used to configure any processed inputs such as:
• Power (S)
• Active power (P)
• Reactive power (P)
• Thermal heat content (ɸ)
• Energy
The change over time of these quantities with respect to the old value can be supervised with
this function.
11.5.3 Setting guidelines
GUID-0D420893-4266-4EED-8790-1FFA0F41C962 v1
Operation
: This setting is used to enable/disable the delta supervision function.
MinStVal
: The minimum start level of the function. If the input is below this level, the function
will be blocked. It should be set depending on the input connected.
DelSt>
: This setting is used to set the start value for delta detection.
DeltaT
: This setting defines the number of execution cycles of old data to be used for delta
calculation. That is, if
DeltaT
setting is set as 6 for a 3 ms function, an 18 ms old value will be
used to compare the change against.
tHold
: This setting defines the pulse length for the start signal. A typical value of this setting is
100 ms.