Name of input Type Default Description Value when
activated
Value when
deactivated
IN7 BOOLEAN 0 Input 7 64 0
IN8 BOOLEAN 0 Input 8 128 0
IN9 BOOLEAN 0 Input 9 256 0
IN10 BOOLEAN 0 Input 10 512 0
IN11 BOOLEAN 0 Input 11 1024 0
IN12 BOOLEAN 0 Input 12 2048 0
IN13 BOOLEAN 0 Input 13 4096 0
IN14 BOOLEAN 0 Input 14 8192 0
IN15 BOOLEAN 0 Input 15 16384 0
IN16 BOOLEAN 0 Input 16 32768 0
The sum of the numbers in column “Value when activated” when all INx (where 1≤x≤16) are
active that is=1; is 65535. 65535 is the highest boolean value that can be converted to an
integer by the IB16 function block.
13.10 Integer to Boolean conversion for six-zone busbar
BCTZCONN
GUID-CCB3768D-0013-47D7-9726-EF8DFE80F433 v1
13.10.1 Identification
GUID-62637FE1-696A-4841-8C76-074565B9CAE2 v1
Function description IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2 device
number
Integer to Boolean conversion for six-
zone busbar
BCTZCONN - -
13.10.2 Application
GUID-221AFC68-C31C-459F-8301-2A8048CB93CE v1
Integer to Boolean conversion for six-zone busbar BCTZCONN is used to transform the zone
connection integer signal of each CT from one bay function block into 7 binary (logical) signals
in the six-zone busbar differential protection. It is intended to facilitate the recording of zone
connection information from each bay function block to the disturbance recorder.
The BCTZCONN function does not have a logical node mapping and is designed to receive only
an integer input locally. If the BLOCK input is activated, it freezes the logical outputs at the last
values.
More specifically, it transfers an integer input ZONCONI to a combination of activated binary
outputs ZONEx (1≤x≤6) and CZ, so that:
6
61
1
2 2
x
x
ZONCONI CZ ZONEx
IECEQUATION16077 V1 EN-US (Equation 91)
where 0≤ZONCONI≤127. Note that when a binary output ZONEx or CZ is activated, it has the
logical value
one
. Otherwise, it has the logical value
zero
.
1MRK 505 370-UEN D Section 13
Logic
Busbar protection REB670 345
Application manual