IEC05000460 V2 EN-US
Figure 15: Example how to set CTStarPoint parameters in the IED
This example is similar to example 1, but here the transformer is feeding just one line and the
line protection uses the same CT as the transformer protection does. The CT direction is set
with different reference objects for the two IEDs though it is the same current from the same
CT that is feeding the two IEDs. With these settings, the directional functions of the line
protection shall be set to
Forward
to look towards the line.
4.2.2.3 Example 3
SEMOD55055-35 v7
One IED used to protect two objects.
Section 4 1MRK 505 370-UEN D
Analog inputs
62 Busbar protection REB670