The equation above also implies that each individual binary output corresponds actually to one
integer, which is presented in the input ZONCONI and can be defined by:
CZ
×2
6
or
ZONEx
×2
x-1
, (1≤x≤6).
Refer to Table 47 for the description of such representations.
Table 47: Integer representations for the binary outputs of BCTZCONN
Output names Type Description
Corresponding integer value
in ZONCONI
When
deactivated
When
activated
ZONE1 BOOLEAN Bay is connected to Z1 0 1
ZONE2 BOOLEAN Bay is connected to Z2 0 2
ZONE3 BOOLEAN Bay is connected to Z3 0 4
ZONE4 BOOLEAN Bay is connected to Z4 0 8
ZONE5 BOOLEAN Bay is connected to Z5 0 16
ZONE6 BOOLEAN Bay is connected to Z6 0 32
CZ BOOLEAN Supervision status of the check zone
on differential zones (Valid only for
feeder bays)
0 64
Figure 194 shows an example how to use BCTZCONN to facilitate the recording of the zone
connection information from one bay, say feeder 01, to a disturbance recorder in ACT for any
six-zone busbar differential protection application.
IEC16000075-1-en.vsdx
IEC16000075 V1 EN-US
Figure 194: BCTZCONN connection example
13.11 Integer to Boolean 16 conversion with logic node
representation ITBGAPC
SEMOD158419-1 v3
13.11.1 Identification
SEMOD167944-2 v4
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Integer to boolean 16 conversion
with logic node representation
ITBGAPC - -
Section 13 1MRK 505 370-UEN D
Logic
346 Busbar protection REB670