SuppressMidPos
when
On
suppresses the mid-position during the time
tIntermediate
of the
connected switches.
The parameter
InterlockCheck
decides if interlock check should be done at both select and
operate, Sel & Op phase, or only at operate, Op phase.
12.3.8.3 Switch (SXCBR/SXSWI)
M16675-3 v8
tStartMove
is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the
tIntermediate
time, the position indication is allowed to be in an intermediate (00)
state. When the time has expired, the command supervision is reset, and a cause-code is given.
The indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
SuppressMidPos
is set to
On
in the SCSWI function.
If the parameter
AdaptivePulse
is set to
Adaptive
the command output pulse resets when a
new correct end position is reached. If the parameter is set to
Not adaptive
the command
output pulse remains active until the timer
tOpenPulsetClosePulse
has elapsed.
tOpenPulse
is the output pulse length for an open command. If
AdaptivePulse
is set to
Adaptive
, it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
tClosePulse
is the output pulse length for a close command. If
AdaptivePulse
is set to
Adaptive
, it is the maximum length of the output pulse for an open command. The default
length is set to 200 ms for a circuit breaker (SXCBR) and 500 ms for a disconnector (SXSWI).
12.3.8.4 Proxy for signals from switching device via GOOSE XLNPROXY
GUID-7C253FE7-6E02-4F94-96C7-81C9129D925D v1
The
SwitchType
setting controls the evaluation of the operating capability. If
SwitchType
is set
to
Circuit Breaker
, the input OPCAP is interpreted as a breaker operating capability, otherwise
it is interpreted as a switch operating capability.
Table 45: Operating capability values for breaker/switches
Value Breaker operating capability, CbOpCap Switch operating capability, SwOpCap
1 None None
2 Open Open
3 Close – Open Close
4 Open – Close – Open Close and Open
5 Close – Open – Close – Open Larger values handled as 4, both Close and Open
6 Open – Close – Open – Close – Open
7 more
tStartMove
is the supervision time for the apparatus to start moving after a command
execution is done from the SCSWI function. When the time has expired, the command
supervision is reset, and a cause-code is given.
During the
tIntermediate
time, the position indication is allowed to be in an intermediate (00)
state. When the time has expired, the command supervision is reset, and a cause-code is given.
The indication of the mid-position at SCSWI is suppressed during this time period when the
position changes from open to close or vice-versa if the parameter
SuppressMidPos
is set to
On
in the SCSWI function.