EQUATION1519 V5 EN-US (Equation 84)
where:  
U2 is the maximal negative sequence voltage during normal operation conditions, plus a margin of
10...20%
UBase
is the base voltage for the function according to the setting 
GlobalBaseSel
The setting of the current limit 
3I2<
 is in percentage of parameter 
IBase
. The setting of 
3I2<
must be higher than the normal unbalance current that might exist in the system and can be
calculated according to equation 
85.
EQUATION1520 V5 EN-US (Equation 85)
where:  
I2 is the maximal negative sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the base current for the function according to the setting 
GlobalBaseSel
11.1.3.4  Zero sequence based
M13683-43 v8
The IED setting value 
3U0>
 is given in percentage of the base voltage 
UBase
. The setting of
3U0>
 should not be set lower than the value that is calculated according to equation 86.
EQUATION1521 V4 EN-US (Equation 86)
where:  
3U0 is the maximal zero sequence voltage during normal operation conditions, plus a margin of 10...20%
UBase is the base voltage for the function according to the setting 
GlobalBaseSel
The setting of the current limit 
3I0<
 is done in percentage of 
IBase
. The setting of 
3I0<
 must
be higher than the normal unbalance current that might exist in the system. The setting can be
calculated according to equation 
87.
EQUATION2293 V3 EN-US
(Equation 87)
where:  
3I0<
is the maximal zero sequence current during normal operating conditions, plus a margin of 10...20%
IBase
is the base current for the function according to the setting 
GlobalBaseSel