QB1
QB2
QA1
QB1
QB2
QA1
QB1
QB2
QA1
QB1
QB2
QA1
ZA
ZB
1
2
8
2
8
8
2
1
REB670(A31-X03)
VERSION OF REB670
NUMBER OF FEEDERS IN THE STATION
( EXCLUDING BUS COUPLER BAY)
REB670(A31 – X03) 3-Phase, 8 Bays, 2 Zones for Double Busbar
Stations with Breaker Failure Protection and End Fault Protection 24AI
7*
BZIT GGIO
87B 3Id/I
BDC GAPC
87B
BDC GAPC
87B
BDC GAPC
87B
BDC GAPC
87B
BDC GAPC
87B
BDC GAPC
87B
BDC GAPC
87B
BCZT PDIF
87B 3Id/I
BUT PTRC
87B 3Id/I
BUT PTRC
87B 3Id/I
BUT PTRC
87B 3Id/I
BZNT PDIF
87B 3Id/I
BZNT PDIF
87B 3Id/I
* With Just one CT in the Bus Section Bay
DRP RDRE
DFR/SER DR
CC RBRF
50BF 3I>BF
CC RBRF
50BF 3I>BF
CC RBRF
50BF 3I>BF
OC4 PTOC
51_67 4(3I>)
OC4 PTOC
51_67 4(3I>)
OC4 PTOC
51_67 4(3I>)
C MMXU
MET I
C MMXU
MET I
C MMXU
MET I
Optional Functions
SMB RREC
79 5(01)
Other Functions available from the function library
BDC GAPC
87B
Q CBAY
Control
C MSQI
MET Isqi
VN MMXU
MET UN
S SIML
71
S SIMG
63
S XCBR
3
Control
S SCBR
Control
V MMXU
MET U
V MSQI
MET Usqi
ETP MMTR
MET
W/Varh
CV MMXN
MET P/Q
DELI SPVC
7I
DELTAI
DELV SPVC
7V_78V
DELTAU
DEL SPVC
7
DELTA
CHM MHAI
ITHD ITHD
VHM MHAI
VTHD UTHD
1EC16000257=IEC16000257=2=en-us=Original.vsd
IEC16000257 V2 EN-US
Figure 7: Configuration diagram for A31, configuration X03
3.1.7 Description of 1 ph packages B20 and B21
SEMOD129275-40 v8
One-phase version of the IED with two low-impedance differential protection zones and twelve
CT inputs B20, B21.
Due to three available binary input modules, the B20 is intended for applications without
need for dynamic Zone Selection such as substations with single busbar with or without
bus-section breaker, one-and-half breaker or double breaker arrangements. Three such
IEDs offer cost effective solutions for such simple substation arrangements with up to
twelve CT inputs.
The B21 is intended for applications in substations where dynamic Zone Selection or
bigger number of binary inputs and outputs is needed. Such stations for example are
double busbar station with or without transfer bus with up to 12 CT inputs. Note that
Section 3 1MRK 505 370-UEN D
Configuration
52 Busbar protection REB670
Application manual