For a bus-coupler bay in section 1, these conditions are valid:
BBTR_OP (sect.1)
DCOPTR (A1A2)
DCOPTR (B1B2)
BBTR_OP (sect.2)
&
VP_BBTR (sect.1)
VPDCTR (A1A2)
VPDCTR (B1B2)
VP_BBTR (sect.2)
EXDU_12 (sect.1)
EXDU_DC (B1B2)
EXDU_12 (sect.2)
VP_BBTR
EXDU_12
en04000483.vsd
&
EXDU_DC (A1A2)
BBTR_OP
>1
&
IEC04000483 V1 EN-US
Figure 154: Signals to a bus-coupler bay in section 1 from any bays in each section
For a bus-coupler bay in section 2, the same conditions as above are valid by changing section
1 to section 2 and vice versa.
12.4.3.4 Signals from bus-coupler
M13553-58 v5
If the busbar is divided by bus-section disconnectors into bus-sections, the signals BC_12 from
the busbar coupler of the other busbar section must be transmitted to the own busbar coupler
if both disconnectors are closed.
Section 1 Section 2
A1A2_DC(BS)
B1B2_DC(BS)
ABC_BCABC_BC
(WA1)A1
(WA2)B1
(WA7)C C
B2
A2
en04000484.vsd
IEC04000484 V1 EN-US
Figure 155: Busbars divided by bus-section disconnectors (circuit breakers)
To derive the signals:
Signal
BC_12_CL Another bus-coupler connection exists between busbar WA1 and WA2.
VP_BC_12 The switch status of BC_12 is valid.
EXDU_BC No transmission error from any bus-coupler bay (BC).
These signals from each bus-coupler bay (ABC_BC), except the own bay, are needed:
Signal
BC12CLTR A bus-coupler connection through the own bus-coupler exists between busbar
WA1 and WA2.
VPBC12TR The switch status of BC_12 is valid.
EXDU_BC No transmission error from the bay that contains the above information.
Section 12 1MRK 505 370-UEN D
Control
308 Busbar protection REB670
Application manual